Typical Condensation Rates in Steam Pipes
Typical Condensation Rates in Steam Pipes - Insulated
Pressure
PSIG (BAR)
Rates in Pounds/Hour (Kg/Hour) per Foot of Pipe with 2 Inches of Insulation
Pipe Diameter (Inches)
0.75
1
1.5
2
3
4
1 (0.069)
0.02 (0.009)
0.03 (0.014)
0.04 (0.018)
0.05 (0.023)
0.06 (0.027)
5 (0.34)
10 (0.69)
0.07 (0.032)
25 (1.7)
0.08 (0.036)
50 (3.4)
0.09 (0.041)
0.11 (0.05)
75 (5.2)
0.14 (0.064)
100 (6.9)
0.12 (0.054)
0.15 (0.068)
125 (8.6)
0.13 (0.059)
0.16 (0.073)
150 (10.3)
0.17 (0.077)
200 (13.8)
0.19 (0.086)
Typical Condensation Rates in Steam Pipes - Bare
Rates in Pounds/Hour (Kg/Hour) per Foot of Bare Pipe at 72 Degrees F (22 Degrees C) Ambient Air
0.21 (0.095)
0.25 (0.113)
0.38 (0.172)
0.46 (0.209)
0.22 (0.1)
0.26 (0.118)
0.41 (0.186)
0.50 (0.227)
0.18 (0.082)
0.24 (0.109)
0.29 (0.132)
0.44 (0.2)
0.53 (0.24)
0.31 (0.141)
0.36 (0.163)
0.65 (0.295)
0.27 (0.122)
0.39 (0.177)
0.66 (0.299)
0.83 (0.376)
0.45 (0.204)
0.54 (0.245)
0.77 (0.349)
1.04 (0.472)
0.35 (0.159)
0.61 (0.277)
0.86 (0.39)
1.11 (0.503)
0.32 (0.145)
0.55 (0.249)
0.68 (0.308)
0.94 (0.426)
1.23 (0.558)
0.42 (0.191)
0.60 (0.272)
0.74 (0.336)
1.03 (0.467)
1.33 (0.603)
0.40 (0.181)
0.49 (0.222)
0.69 (0.313)
0.81 (0.367)
1.19 (0.54)
1.50 (0.68)
BTU Comparisons | Properties of Saturated Steam | Steam Capacity | Temperature Conversions | Typical Condesation Rates | Volumes of Gas | Water Flow | Water Flow-Continued | Legal Information